dc.description.abstractResumo: Parâmetros de controle tais como teor de umidade e valores de CBR foram estabelecidos em obras de subestação de energia, com objetivo de assegurar capacidade de suporte e recalques adequados de aterros. O CBR mínimo adotado, igual a 10%, foi tomado como aceitável e diversas obras realizadas nos últimos anos têm demonstrado bom desempenho. O objetivo do presente estudo foi verificar a pertinência de tais parâmetros especificados, por meio de testes de campo (provas de carga sobre placa) e em laboratório (cisalhamento direto, adensamento, CBR e caracterização do solo), focando aterros executados em alguns locais do Estado do Paraná. Tentativas de correlacionar os valores de CBR com alguns parâmetros geotécnicos mais representativos de capacidade de suporte foram feitas e conclusões são apresentadas, mostrando tendências razoáveis entre CBR e coeficiente de recalque, por exemplo, em especial para solos mais arenosos.pt_BR
dc.description.abstractAbstract: Some common geotechnical parameters, such as water content and CBR value, were tentatively established to help provide adequate support and settlement fill behavior for electric substation structures. A minimum CBR adopted by an electric power company, equal to 10%, has been used for some time and was checked in real works. The objective of the present study was to verify the correctness of such simple specification by means of field plate load tests and laboratory tests (consolidation, direct shear, compaction, CBR and soil characterization), emphasizing such structures built in a few sites around Paraná State. Attempts to correlate CBR values with other considered more representative geotechnical parameters of fills were made and some conclusions are presented, showing so far reasonable tendency between CBR and deformation modulus, as well as with bearing capacity, for example, mainly for sandy soils.pt_BR
dc.format.extent175f. : il., grafs., tabs.pt_BR
dc.format.mimetypeapplication/pdfpt_BR
dc.languagePortuguêspt_BR
dc.relationDisponível em formato digitalpt_BR
dc.subjectSolos - Umidadept_BR
dc.subjectAterrospt_BR
dc.subjectSolos - Compactaçãopt_BR
dc.subjectEngenharia Civilpt_BR
dc.titleAnálise de especificações de aterro e correlação entre CBR e capacidade de carga em solos compactadospt_BR
dc.typeDissertaçãopt_BR


Arquivos deste item

Thumbnail

Este item aparece na(s) seguinte(s) coleção(s)

Mostrar registro simples